Both are approved drain, waste and vent materials under IPC 2021Tables 702.1 and 702.2, above and below ground. The choice turns on three things the bore does not change: how loud the stack is, what happens where it passes through a fire-rated floor, and what is already in the building. The adopted edition and any local amendment are set by your authority having jurisdiction (AHJ).
Best overall
PVC, on most houses
Light, solvent-welded and on every code table, and the easiest material to handle where no fire-rated assembly is crossed.
Best for quiet, rated stacks
Cast iron
Measurably quieter in an industry-commissioned test, and it qualifies for the IBC metal-pipe firestopping exceptions.
Best for repairs
PVC, with a shielded transition
IPC 2021 §705.16 allows it through a mechanical joint. Size the coupling to the iron you actually have.
The matrix
IPC 2021Tables 702.1, 702.2, 308.5 and §705; movement, temperature and noise rows per CISPI and Charlotte Pipe, read 2026-10-18
Factor
Cast iron
PVC
Pipe standard
ASTM A74 (hub); A888 / CISPI 301 (hubless)
ASTM D2665; F891 cellular core
Joining
No-hub coupling, gasket or lead and oakum
Purple primer (F656) + cement (D2564)
Coupling standard
CISPI 310, ASTM C1277 or C1540
Not applicable
Hanger spacing, horizontal
5 ft (10 ft with 10 ft lengths)
4 ft
Support spacing, vertical
15 ft
10 ft, guide midway at 2" and under
Movement per 100 °F change
Under 1" per 100 ft
About 3.6" per 100 ft
Max working temperature
212 °F with C564 gaskets
140 °F
Combustibility
Non-combustible
Combustible
Noise, 3" DWV
Quieter by 6–10 dBA in one test
Louder
Handling
Heavy; cut with a snap cutter
Light, saw and cement
Read the noise number for what it is
The 6–10 dBA figure (an average of 8 dB on 3" pipe, open or behind drywall) comes from a study by MJM Acoustical Consultants that the cast iron industry commissioned and reports in its own handbook. It is the only measured comparison we could find, and the direction matches what installers report, but treat the size of the gap as one test rather than a rating. Isolating hangers and keeping drains out of bedroom walls also matter.
Fire and firestopping
This is the difference that decides stacks in multi-story buildings, and it is a building code question before it is a plumbing one. IPC 2021307.3 and 315.1 send every penetration of a fire-resistance-rated assembly to Section 714 of the International Building Code (IBC). What 714 then asks for depends on what the pipe is made of.
Cast iron is ferrous and non-combustible. IBC 2021714.4.1 (walls) and 714.5.1 (floors) carry exceptions written for "steel, ferrous or copper" pipe: in a concrete or masonry wall, a pipe of up to 6" nominal through an opening of no more than 144sq in may be packed with concrete, grout or mortar for the full thickness, and a fill that keeps flame and hot gases from passing under the ASTM E119 or UL 263 fire test is also accepted. PVC qualifies for none of those exceptions. A plastic pipe burns out of its own hole, so every rated penetration needs a tested through-penetration firestop system.
IBC 2021 §714.4.1, §714.4.1.2, §714.5.1, §714.5.1.2. Plenum rules sit in the mechanical code; that row is per Charlotte Pipe's published comparison.
Rated penetration
Cast iron
PVC
Combustibility
Non-combustible
Combustible
IBC 714.4.1 / 714.5.1 metal-pipe exceptions
Available
Not available
Tested firestop system (ASTM E814 / UL 1479)
One option
Required
Rating the system must carry
F rating, plus T rating on floors
F rating, plus T rating on floors
Return-air plenum
Permitted (non-combustible, ASTM E136)
Excluded (fails the 25 / 50 E84 limits)
A tested system under IBC 2021714.4.1.2 or 714.5.1.2 is tested to ASTM E814 or UL 1479 at a positive pressure of 0.01in of water, and its F rating must meet the rating of the wall it passes through. On floors both the F and the T rating must be at least 1hour and not less than the floor's own rating; the T rating is waived for penetrations inside a wall cavity and for floor, tub and shower drains in a concealed horizontal space. For plastic that usually means a listed collar or wrap sized to the pipe — a part with a listing number that the inspector will want to see on the submittal.
Keep the transition out of the hole
The cast iron industry's suggested firestop specification says combustible pipe should not join non-combustible pipe inside a rated penetration unless the transition itself is shown to comply, and that unshielded couplings should not be used there. Make the change of material a clear distance away from the assembly, and match the firestop listing to the pipe that actually passes through.
Expansion, support and standards
PVC moves. At about 3.6"per 100 ft per 100 °F it grows several times as much as iron, which matters on a tall stack taking hot discharge or a long run in an unconditioned space. IPC 2021305.2 requires piping to be installed so expansion and contraction cannot overstress it, and 308.8 limits expansion joint fittings to places that genuinely need them. Offsets that let the pipe flex are the usual answer. Iron's movement is small enough that it rarely enters the conversation.
Support goes the other way. Table 308.5 lets iron hang at 5 ft (or 10 ft where 10 ft lengths are used) and stand 15 ft between vertical supports, against 4 ft and 10 ft for PVC. Slope is identical for both; the drain slope calculator does not care which you pick.
On standards, check the print line on the pipe. Schedule 40 marked only ASTM D1785 is pressure pipe and does not appear in the IPC 2021 drainage tables; DWV wants D2665, F891 or F1488. The IPC basics guide covers how those tables are adopted, and IPC vs UPC covers what changes if your jurisdiction runs the other code.
Where each one wins
Cast ironA888 / A74
The stack material for multi-story and multifamily work, where a drain runs past bedrooms and through rated floors. It is quiet, it does not burn, it barely moves with temperature, and a non-combustible pipe opens the simpler firestopping routes in IBC 714. Engineers on those buildings often specify it; a jurisdiction may limit plastic DWV by building type, so ask before you price plastic.
Against it: weight, slower handling, and older iron that has scaled inside or cracked — which is why so many repairs end up in PVC.
PVCD2665 / F891
The default on most single-family work. It is light, it cuts with a saw, the joint is primer and cement, and it does not corrode in sanitary service. Below ground it performs when it is bedded and backfilled as the manufacturer specifies; a flexible pipe on a poor trench fails early.
Against it: louder in a wall, it moves with temperature, it tops out at 140 °F, and every rated penetration needs a tested firestop system with a listing to match.
Repairing old cast iron with PVC
Most of the time this comparison is not a new-build choice at all. It is a cracked hub, a rotted section of building drain or a leaking stack in a house plumbed in iron, and the question is whether PVC can go in for the length you are cutting out. Under the IPC it can, provided the joint between the two is the right kind.
IPC 2021705.16 requires joints between different materials to be a mechanical joint of the compression or mechanical-sealing type conforming to ASTM C1173, ASTM C1460 or ASTM C1461, with an elastomeric seal. 705.16.4 then says a plastic pipe meets a cast iron hub with a caulked joint or a mechanical compression joint, and meets other materials through an approved adapter fitting. Solvent cement has no part in it: the only solvent joint the section allows between materials is one ABS-to-PVC joint where the building drain becomes the building sewer, which is a different story covered in ABS vs PVC for DWV.
Cutting PVC into a cast iron lineIPC 705.16
The coupling is sized to both outside diameters it joins; the iron is hung on both sides first.
Two things catch people out. First, hub-and-spigot iron to ASTM A74 comes in two classes, service weight (SV) and extra heavy (XH), and the extra wall is added to the outside, so the two have different outside diameters. Measure the pipe you actually have before you buy the coupling; a transition coupling is sized to both diameters it joins. Second, iron is heavy and the run above or beside the cut is held up partly by the piece you are about to remove. Hang or clamp it on both sides first, so the pipe cannot drop or shear a joint further along once it is cut.
What the repair costs, without a made-up number
We could not verify a current published cost band for cast iron replacement on the day this page was written, so there is no dollar figure here. The price is set by access more than by material: iron in an open basement ceiling is the cheap case, the same length under a slab means breaking and patching concrete, and a stack inside finished walls on an upper floor means opening the walls and, where it passes through a rated floor, firestopping it again. A permit is normally required either way — see plumbing permit cost — and if the iron runs out to the street, the sewer line replacement cost guide covers the outside part of the job.
Do not just glue to it
IPC 2021 §705.16 wants a mechanical joint between PVC and cast iron, so a solvent-cement or adhesive joint does not comply. Use an approved mechanical transition coupling, or a caulked joint or compression gasket where PVC goes into a sound cast iron hub.
Buying checklist
Before you choose or cut
Ask the AHJ which edition is adopted and whether plastic DWV is limited for this building type.
Map every rated wall and floor the run crosses; price a listed firestop system per plastic penetration.
For a stack past bedrooms, weigh the noise gap and plan isolating hangers either way.
Read the print line: D2665 or F891 for PVC, A888 / CISPI 301 or A74 for iron.
Repairing iron: measure the outside diameter, buy a shielded transition coupling to match, hang both sides.