Plumbing rough-in dimensions

Updated 2026-09-04 · 9 min read

Fixtures and repairs
Isometric cutaway of a bathroom rough-in with stub-outs at set heights
Bathroom wall rough-in cutaway: stub-outs at height, framing and lines floated apart.

The heights and offsets

Rough-in is the moment the wall stops being adjustable. Every dimension below is measured from the finished floor and the finished wall, not from the subfloor and the studs — the single commonest rough-in error is forgetting the thickness of the tile and the mortar bed.

Common residential rough-in dimensions, AFF = above finished floor
FixtureDrainSuppliesNote
Lavatory18"–20" AFF20"–22" AFF, 4" each side of centreHigher for a vessel bowl
Kitchen sink16"–20" AFF22" AFF, 8" apartClear the disposal
Water closet12" rough-in from wall6"–8" AFF, 6" left of centre10" and 14" roughs also exist
Tub / shower valveTrap at floor28"–32" AFF for a tubHigher in a walk-in shower
Shower head72"–80" AFFSet to the tallest user
Clothes washer box32"–36" AFFIn the box, 32"–36" AFFStandpipe height is code-set

Confirm against the fixture, always

These are the common values, not a specification. Every manufacturer publishes a rough-in sheet for the actual model, and a wall-hung or a vessel installation departs from all of them. The fixture's own sheet wins.

Clearances the code sets

Fixture spacing is a code requirement, not a preference. A water closet needs a minimum clear width centred on the bowl and a minimum clear space in front of it; a lavatory needs clearance in front. Those numbers decide whether a bathroom layout is legal before any pipe is roughed.

Draw them on the plan. A layout that works on paper at 14 inches of centreline clearance and needs 15 is a layout that gets rejected at plan review or, worse, at final.

Roughing the DWV, not just the supplies

The supplies are the easy half. The drain has to leave at the right height, run at the right slope, and reach its vent inside the trap arm limit — which for a 1-1/2" lavatory trap is 6 ft. Work that backwards from where the stack is before you fix the fixture location.

Fixtures and repairs
Isometric detail illustration for the plumbing rough in dimensions guide
Bathroom wall rough-in with stub-outs at their set heights.

Protecting the pipe in the frame

Anything within an inch and a quarter of the face of a stud gets a nail plate. That rule exists because the drywall screw that finds a PEX line does so six months later, behind paint, and the repair is the whole wall.

Support at the code interval for the material, sleeve where pipe passes through concrete, and keep supply lines out of exterior wall cavities in cold climates — the last one is a freeze decision made at rough-in and unmakeable afterwards.

Test before it is covered

The rough inspection is a pressure test on the DWV — water or air, to the pressure and duration your jurisdiction names — and a pressure test on the supplies. Both have to hold while the inspector watches, and both are far easier to fix now than after the drywall.

Photograph the open wall before it closes: stub-out heights, the nail plates, the vent arrangement. It costs two minutes and it answers every question the tiler, the cabinet fitter and the next plumber will ask.

Code violation

Covering rough plumbing before its inspection is reopened at your cost. Photographs do not substitute for the inspection, however good they are.